    PLC Program for Automatic Parameter Initialization When Power UP

       (0 reviews)

    xiangjinjiao

    This is a PLC Program for Automatic Parameter initialization when power up.

    Parameter Initialization When Power UP

    Problem Description

    In many applications, it is necessary to initialize some data when the machine is powered up.

    Sometimes due to power failure, the value in some parameters becomes zero.

    Due to this problem, the operator has to feed all data again or every time during power failure.

    When the machine gets powered up, at that time necessary parameters should be initialized automatically.

    Here we discuss this issue with some basic ladder logic.

    Problem Diagram

    66-1.gif

    Problem Solution

    In this case, we need to write the logic in the PLC program so all parameters will be initialized automatically.

    We can also set a manual initialization button so the operator can initialize data while the machine operation is running.

    Here we will consider the machine set speed as data and it will be initialized automatically when the machine turns on.

    If the operator wants to reinitialize the set speed during the running cycle then he needs to do it through the initialization button.

    PLC Ladder diagram

    Here is the PLC program Automatic Parameter initialization when powered up.

    66-2.gif

    List of PLC inputs/outputs

    • Inputs List
    • Parameter Initialization Button : I0.0
    • MW10 : Set Speed form Display

    Outputs List

    • Mw12 : Speed for drive

    Program Description

    • For this application we use S7-1200 PLC and TIA portal software for programming.
    • This logic is used for parameter initialization.
    • For first scan, we used here S7-1200 facilities of system Memory. Every PLC have its own system memory.
    • Always ON bit, always OFF bit, first scan bit, and diagnostic status changed are the system memory for S7-1200 PLC.
    • We can configure any memory address “M” for system memory. Here we configured M1.0 for first scan bit which is used for parameter initialization.
    • We write for parameter initialization in Network 1. Here we use NO contact of First scan bit (M1.0) for moving initial 5 RPM in MW12(Speed for drive).By using MOVE instruction 5 RPM will be moved in MW12 . Add NO contact of Parameter Initialization Button (I0.0) for moving Initial 5RPM in MW12 (Speed for drive) manually.
    • For editing data manually in running cycle we write logic in Network 2. Here operator can enter data in MW10 (SET SPEED) from the display and it will go in MW12(Speed for drive).
    • For Example, Say we need to enter 100 RPM speed from display it will be written in word MW10 (Set Speed from display) and as per logic it will be moved in MW12 (Speed for drive), so motor will run on 100 RPM.

    Runtime Test Cases

    66-3.gif

    Note: The above PLC Logic provided for basic idea about application of PLC Program for Automatic Parameter Initialization when Power UP. The Logic is limited and not complete application.

    Sign in to follow this  


    User Feedback

    Create an account or sign in to leave a review

    You need to be a member in order to leave a review

    Create an account

    Sign up for a new account in our community. It's easy!

    Register a new account

    Sign in

    Already have an account? Sign in here.

    Sign In Now

    There are no reviews to display.


Apply for friendship links:WhatsApp or E-mail: admin@plchmis.com
×
×
  • Create New...