Jump to content
  • Sign in to follow this  

    PLC Program to Drain Same Products from Two Tanks

       (0 reviews)

    caixiaofeng

    This is a PLC Program to drain the same products from two tanks. Learn the PLC programming with this simple example.

    Drain the Same Products from Two Tanks

    Problem Description

    Two tanks are filled with same products. Draining materials from these two tanks is depended on the requirement of storage tank.

    Implement logic for this system in PLC using ladder diagram.

    Problem Diagram

    86-1.gif

    PLC Example Solution

    Here two tanks are used for the system. For level measurement, two sensors are used (level low sensors). As shown in figure we use here two pumps for transferring the materials from tanks (Tank 1 & Tank 2) to storage tanks.

    Here we will use level transmitter for storage tank level measurement. PUMP 1 & PUMP 2 will be controlled by level transmitter feedback.

    Here we used two pumps for smooth operation. Both pumps will be operated when level of the storage tanks is detected below its limit.

    Note:-Here we are consider simple automation for this system. Level transmitter is used in this system and it will measure the level of the storage.

    Storage tank is taken of 500cm height for simplicity and level transmitter feedback is 4 to 20mA.

    We will use PLC S7-300 for this application. We will use scaling for programming purpose.

    List of I/Os

    List of inputs

    • Cycle START:- I0.0
    • Cycle STOP :- I0.1
    • Level low of tank 1 :- I0.2
    • Level of tank 2 :- I0.3

    List of outputs

    • Pump 1 :- Q0.0
    • Pump 2 :- Q0.1

    M memory

    • Cycle ON bit :- M0.0
    • Analog value from the transmitter :- MW10 (INT)
    • Analog value from the transmitter :- MD100 (DINT)
    • Multiplication value :- MD104
    • Actual water level (cm) :- MD108

    PLC Ladder Diagram for draining the same products from two tanks

    86-2.gif
    86-3.gif
    86-4.gif
    86-5.gif
    86-6.gif86-7.gif

    Program Explanation

    For this application, we used S7-300 PLC and TIA portal software for programming.

    Network 1:
    we used latching circuit for cycle ON (M0.0) output.it can be started by pressing START PB (I0.0) and stop by pressing STOP PB (I0.1).

    Network 2:
    Here actual count or value coming from the transmitter is current (4 to 20mA) so by using analog input channel in the PLC we can convert it into digital count. This digit is in INT (MW10) format so we need to convert it into DINT (MD100) for calculation or multiplication.

    Network 3:
    DINT value (MD100) is multiplied with max height (500cm) of the tank for calculation purpose.

    Network 4:
    Multiplied value (MD104) is divided by max count of the analog module (27648).And final actual height is stored in MD108.

    Network 5:
    Here we used comparator for PUMP 1 (Q0.0).During requirement of the material PUMP 3 will be operated by operator, water level height will decrease.

    So as per our automation or system we need to fill storage tank, pump 1 will be started if water level is less than its limit (here we have taken 480cm).

    Note:- PUMP 1 should be stop if level low (I0.2) of the tank 1 is detected.

    Network 6:
    Here we used comparator for PUMP 2 (Q0.1). During requirement of the material PUMP 3 will be operated by operator, water level height will decrease. So as per our automation or system we need to fill storage tank, pump 2 will be started if water level is less than its limit (here we have taken 480cm).

    Note:- PUMP 2 should be stop if level low (I0.3) of the tank 2 is detected.

    During all function cycle should be ON.

    Note:- Above application may be different from actual application. This example is only for explanation purpose only. We can implement this logic in other PLC also. This is the simple concept of drainage system, we can use this concept in other examples also.

    All parameters considered in example are for explanation purpose only, parameters may be different in actual applications. Also all interlocks are not considered in the application.

    Result

    86-8.gif

    Sign in to follow this  


    User Feedback

    Create an account or sign in to leave a review

    You need to be a member in order to leave a review

    Create an account

    Sign up for a new account in our community. It's easy!

    Register a new account

    Sign in

    Already have an account? Sign in here.

    Sign In Now

    There are no reviews to display.


Apply for friendship links:WhatsApp or E-mail: admin@plchmis.com
×
×
  • Create New...